The Emergency Operation Standpipe: |
|
This component of the Sewer Pump
Station is a “last resort” part of the design. This is intended to be used only if all
three pumps have failed or cannot be used because of a complete power failure
and generator failure. Levels in the
Wetwell are rising and overflowing into the Overflow Tank, and a repair will
take too long.
The Standpipe is an Auxiliary Pump Connect where one could borrow,
purchase, or rent a portable gasoline
driven pump and use that pump in lieu of the normal pumps. These portable pumps usually have a large
suction hose attached to them that can be submerged in the fluid to be
pumped. One would drop the suction
hose into the Wetwell and be ready to pump.
The Cam Lock fitting on the Standpipe fits many standard portable pump
discharge hoses. One would connect the
discharge hose to this fitting.
The procedure then would be to lift the Valve Box covers on the Pump
#1 and #2 Outlet Valve Box (the blue valves) and close both of those
valves. Then lift the cover on the
Standpipe Valve (see below) and open that valve.
Once the Standpipe Valve is open, the portable pump with its suction
hose in the Wetwell can start to pump the fluid from the Wetwell into the
Force Main and on to the Hotel.
|
|
Cam Lock fitting for portable pump
discharge hose |
Click
here to download Publisher file
|
Valve Box cover for Standpipe
Valve. Lift the cover so that the
valve can be opened. This valve is
normally closed except in emergency situations. |
|
Wetwell |
|
Page 15 |